HVAC & Refrigeration

Modeled: display case retrofit, regional supermarket

Full-line grocery — reach-in and walk-in doors re-glazed across the refrigerated aisles

Modeled scenario using THERMGLASS calculators — not a completed installation. Figures are calculation-derived; see the outcome note at the end of this page.

Share

The Problem

More than sixty reach-in and walk-in glass doors line the store's refrigerated aisles, nearly all of them legacy single-pane units with anti-sweat heater wire in the frame. The heaters run continuously — typically 7 to 12 watts per linear foot of door perimeter, twenty-four hours a day — fighting a fog cycle that returns with every defrost and every humid summer afternoon.

Each watt was effectively paid twice. The heater's electricity lands on the utility bill directly, and the heat it adds to the case lands again as compressor work removing it. Conductive heat gain through the glass door is a dominant load in refrigerated display cases, and it compounds at summer peak — when demand charges price every additional kilowatt at a premium.

The merchandising cost sat on top of the energy cost. Fogged doors hide the stock behind them in the highest-turn aisle of the store, and open-front cases were never on the table — the load they add is exactly what the retrofit was meant to remove. The doors needed to stay closed, clear, and selling.

The Solution

The refit re-glazes reach-in and walk-in doors with vacuum insulated glass on the standalone build — a design-intent whole-door U-factor of 0.081 Btu/h·ft²·°F against the 0.28 Btu/h·ft²·°F reference double-pane low-e IGU used across the refrigeration performance basis. The slim profile drops into door frames designed for standard double-pane IGU, without frame replacement.

Because the inner glass surface holds near store ambient instead of case temperature, condensation resistance ratings of 77–94 (design intent) keep the surface above the store dew point across standard operating conditions — so the anti-sweat heater wiring can be reduced or removed entirely. In high-humidity aisles, an ITO-coated heated glass option remains available as a trim heat source. NSF/ANSI 7 compliance is issued to the completed OEM cabinet, which this glazing is engineered to support — not to the glass component alone.

The business case came from the refrigeration ROI engine, which models exactly this door decision: conduction heat gain Q = U × A × ΔT × hours, compressor energy at the case COP, and anti-sweat heater savings from the ASHRAE Refrigeration Handbook 2022 §15 heater inputs — heater wattage per meter of perimeter and the fraction of doors heated — priced against the store's electricity tariff.

Modeled Outcomes

Figures are modeled outputs calculated from published methodology and the THERMGLASS ROI engine — not laboratory or field measurements. Run the linked calculator for project-specific numbers.

Center-of-glass U-factor

0.081 vs 0.28 Btu/h·ft²·°F

Design-intent standalone VIG against the reference double-pane IGU — a 71% conductive heat-gain reduction at the door; Hybrid VIG (0.044 Btu/h·ft²·°F) reaches 84% where CR 85+ is required.

Anti-sweat heaters

Reducible or removable

With the glass surface held above the store dew point, heater wiring (typically 7–12 W per linear foot of door perimeter) can be reduced or, in cooler-duty aisles, removed — an additional 15–25% reduction in total door energy on top of the conduction cut.

Combined door energy

71–84% lower

Calculated combined reduction versus the reference IGU across application types and ambient conditions — conduction plus heater elimination, on the published refrigeration performance basis.

Compressor load

≈$1,038/yr at defaults

The refrigeration ROI engine's default scenario (10 doors at 0.84 m², heated double-pane baseline, hybrid VIG, ΔT 40 K, 24 h/day, COP 2.5, $0.12/kWh, glass heater share 50%) returns ≈$1,038/yr combined conduction-plus-glass-heater savings and a ≈3.7-year payback; the linked calculator prices your case count, COP, and tariff.

Put numbers on your project

Model the same glazing decision for your own project — dimensions, climate, and rates in, project-specific savings out.

Technical Reading

Cold Storage

Vacuum Glass for Supermarket Refrigeration Doors

Vacuum glass cuts display-door heat gain and dramatically reduces anti-sweat heater duty — door U-values and heater watts, per ASHRAE Refrigeration 2022.

Read the guide
Cost & ROI

HVAC Savings From Vacuum Glass: The Peak-Load Math

How lower U-values cut HVAC tonnage and peak demand charges, with the sizing math and a worked peak-load example from the free THERMGLASS ROI engine.

Read the guide
Cold Storage

Cold Storage Efficiency: The Hidden Cost of Poor Door Glazing

Quantifying compressor energy waste from high-U glass in walk-in coolers and freezers using ASHRAE Refrigeration 2022 load models (Ch. 24) — with real payback calculations.

Read the guide