Vacuum Insulating Glazing

CSI MasterFormat Section 08 81 00 · THERM GLASS GROUP LLC · Philadelphia, PA · thermglass.com

1. Summary

Provide vacuum insulating glazing (VIG) units for glazed openings as shown on the drawings and specified in this section. Units consist of two glass lites separated by a sub-millimeter evacuated spacer with a warm-edge perimeter seal and a flush frit seal.

2. Product Description

3. Performance Requirements

PropertyValueBasis
Center-of-glass U-factor (COG)0.46 W/m²·KEN 673 calculation
Whole-window Uw (architectural framing basis)0.73 W/m²·KISO 10077-1 derived; thermally broken aluminum frame, 20 percent frame fraction
U-factor (US basis)0.13 Btu/h·ft²·°FISO 10077-1 derived, pre-NFRC

Certification testing to NFRC 100/500 and EN 673 type-approval is in progress. Values above are calculated and pre-certification; use them for design comparison only until certified data is published.

4. Execution

  1. Verify openings and framing prior to glazing installation.
  2. Install units per manufacturer glazing instructions; support units on compatible setting blocks.
  3. Do not field-cut, drill, or edge-grind VIG units. Edge damage voids the vacuum cavity.
  4. Seal perimeter glazing with compatible neutral-cure sealants; verify sealant compatibility with the frit edge seal.

5. References

6. Submittals

© THERM GLASS GROUP LLC. This document is provided for specification use. Values designated pre-certification are calculated and subject to revision upon completion of certification testing.