Vacuum Insulating Glazing
CSI MasterFormat Section 08 81 00 · THERM GLASS GROUP LLC · Philadelphia, PA · thermglass.com
1. Summary
Provide vacuum insulating glazing (VIG) units for glazed openings as shown on the drawings and specified in this section. Units consist of two glass lites separated by a sub-millimeter evacuated spacer with a warm-edge perimeter seal and a flush frit seal.
2. Product Description
- Standalone VIG stack: 6.3 mm, 8.3 mm, or 10.3 mm overall thickness (3, 4, or 5 mm lites respectively), with flush perimeter frit seal.
- Hybrid assemblies: VIG lite laminated or IGU-combined, overall thickness approximately 20.3–26 mm, for applications requiring laminated safety glazing or acoustic performance.
- Warm-edge vacuum cavity; no conductive metal edge spacer across the sightline.
3. Performance Requirements
| Property | Value | Basis |
| Center-of-glass U-factor (COG) | 0.46 W/m²·K | EN 673 calculation |
| Whole-window Uw (architectural framing basis) | 0.73 W/m²·K | ISO 10077-1 derived; thermally broken aluminum frame, 20 percent frame fraction |
| U-factor (US basis) | 0.13 Btu/h·ft²·°F | ISO 10077-1 derived, pre-NFRC |
Certification testing to NFRC 100/500 and EN 673 type-approval is in progress. Values above are calculated and pre-certification; use them for design comparison only until certified data is published.
4. Execution
- Verify openings and framing prior to glazing installation.
- Install units per manufacturer glazing instructions; support units on compatible setting blocks.
- Do not field-cut, drill, or edge-grind VIG units. Edge damage voids the vacuum cavity.
- Seal perimeter glazing with compatible neutral-cure sealants; verify sealant compatibility with the frit edge seal.
5. References
- EN 673 — Glass in building: determination of thermal transmittance (U value) by calculation.
- ISO 10077-1 — Thermal performance of windows, doors and shutters: calculation of U-factors.
- NFRC 100/500 — procedures for determining fenestration thermal and solar-optical properties (testing in progress).
6. Submittals
- Product data including thickness, U-factor basis, and edge-seal description.
- Glazing details and setting-block layout.
- Pre-certification performance statement as included in Section 3 of this specification.
© THERM GLASS GROUP LLC. This document is provided for specification use. Values designated pre-certification are calculated and subject to revision upon completion of certification testing.